Improving Slip Resistance in a Multi-Storey car park

In 2024, a client in Crawley completed the construction of a new multi-storey car park. As part of the handover process, slip resistance testing was undertaken using the Pendulum Test Method.

Initial testing showed that all trafficked floor areas achieved Pendulum Test Values (PTVs) above 36, indicating a low slip potential. However, it was noted that some of the painted wayfinding markings, including line markings and directional features, recorded lower values, with certain areas achieving PTVs of around 40. While these results were acceptable at the time, it was identified that the slip resistance of the markings could reduce over time due to wear from pedestrian and vehicle traffic.

During the winter months of 2024, several users of the car park reported slipping incidents near the entrance area. Investigation identified that the affected location contained yellow hatched markings and a zebra crossing, which were frequently exposed to wet weather and therefore presented a higher slip risk.

Following further assessment, two potential solutions were identified:

Option 1: Mechanical Surface Grinding

The painted surface markings were lightly ground to create a more textured finish. This improved the slip resistance of the affected areas; however, the long-term durability of the treatment could not be guaranteed as ongoing traffic would continue to wear the surface.

Option 2: Anti-Slip Surface Treatment

The affected markings were thoroughly cleaned before applying a clear acrylic primer. A fine quartz aggregate was then broadcast onto the wet primer, creating an additional slip-resistant surface layer.

This solution provided several benefits:

  • Significantly improved slip resistance
  • Maintained the original appearance and visibility of the line markings
  • Minimal disruption to the client
  • More durable long-term performance than mechanical grinding alone

Post-treatment testing recorded PTV values exceeding 45, providing a substantially improved level of slip resistance in wet conditions.

The Result

The enhanced surface significantly reduced the slip risk in the affected area while preserving the visual appearance of the car park's wayfinding system. The client was extremely satisfied with the outcome and gained confidence that the entrance area remained safe for both pedestrians and visitors during wet weather conditions.

Preventing a Slip Hazard at a Lift Threshold

In 2025, we were engaged on a project where new lifts had been installed within a newly built staircase. The approved design included a 20 mm change in level between the landing and the lift threshold. To create a neat and functional transition, the contractor proposed installing aluminium checkered plates as a ramped threshold solution.

Whilst carrying out slip resistance testing elsewhere on the project, we were informed of the contractor's intention to use checkered plate in this location. Based on our experience, we immediately raised concerns, as many commonly available checkered plates perform poorly in wet conditions and often fail to achieve acceptable slip resistance values.

To demonstrate the risk, we requested a sample of the proposed checker plate before installation. Pendulum testing was carried out, which recorded a wet Pendulum Test Value (PTV) of just 22, significantly below the level typically considered to present a low slip potential.

The results highlighted a serious risk, particularly as the threshold would be used daily by pedestrians, including individuals with reduced mobility, and would be subject to wet weather conditions.

Our Recommendation

Drawing on our expertise in resin flooring systems, we proposed an alternative solution using a specialist anti-slip resin finish. The options considered included:

  • Epoxy Resin Systems
  • Polyurethane (PU) and Polyurethane-Acrylic Systems
  • Polymethyl Methacrylate (PMMA) Systems

To achieve the required slip resistance, a fine quartz aggregate was incorporated into the resin system, creating a durable, attractive, and highly slip-resistant walking surface.

Benefits of the Solution

  • Significantly improved slip resistance in both dry and wet conditions
  • Created a safe transition between the landing and lift threshold
  • Durable and suitable for high pedestrian traffic areas
  • Visually attractive and professional finish
  • Reduced the risk of slips, trips and potential liability claims
  • More suitable for accessibility requirements than untreated checker plate

The Result

The contractor was able to avoid installing a flooring solution that would have presented a significant slip risk to building users. By selecting a resin-based anti-slip system with a quartz finish, the threshold achieved the required functionality while providing a far safer walking surface.

This case highlights the importance of testing flooring materials before installation rather than assuming they are fit for purpose. A product that appears suitable can sometimes perform poorly when scientifically assessed, particularly in wet conditions.

 